Plug-In Solar in Colorado

The law, and what it means for your design.

Plug-in solar by state › Colorado

In effect

Law checked Oct 13, 2026 against HB 26-1007 final passed text · Last change: HOA rules dated January 1, 2027; sale, lease or rent; codes and liability added · Change log

Colorado allows the largest plug-in systems in the country, up to 1,920 W, and took effect August 12, 2026. Above 391 W, plan on a licensed electrician: only devices of 391 W or less are exempt from the state’s solar installation law. And 1,920 W is more than a standard 15 A outlet circuit is built for.

What you can build today

Up to 391 W: yes. A listed microinverter on a standard outlet. The law waives code and listing rules that would require rewiring at this size (§ 40-2-140(5)).

Over 391 W: no plug-in path yet. No complete system is certified, and the certificates call for a locking outlet and two-way GFCI not on sale. A permitted, hardwired install is the route.

Always an option: a permitted, hardwired system under NEC 690 and 705 with your utility’s approval, or an off-grid power station that never connects to house wiring. UL Solutions notes the 2026 NEC “does not recognize the use of plug-in photovoltaic (PIPV) modules”; NFPA expects them in the 2029 edition (source). Where a law requires the NEC and gives no size waiver, the inspector decides. Sun Safe’s reading, not legal advice.

Limit
1,920 W to the grid, with a 391 W small-device tier
Law
HB 26-1007
Signed
May 7, 2026
Effective
August 12, 2026

What the law says

Size limit1,920 W supplied to the grid
How it’s measuredOne system per address, and no more than one device per wall outlet.
391 W tierDevices of 391 W or less are exempt from the state’s solar installation requirements and from code or listing rules that would require rewiring.
Above 391 WPlan on a licensed electrician. The law exempts only devices of 391 W or less from the solar installation requirements of C.R.S. 40-2-128 (§ 40-2-140(5)). Our reading, shared by utilities such as La Plata Electric: above 391 W, 40-2-128 applies: on-site supervision by a NABCEP-certified PV professional or a licensed electrician, and all work on the AC side of the inverter by an electrical contractor employing a licensed journeyman electrician or residential wireman.
ListingLabeled and listed by an NRTL. From January 1, 2027, devices over 391 W can’t be sold, leased or rented unless UL labeled and listed (§ 40-2-140(6)).
Outage protectionRequired.
Utility noticeThe utility may ask you to report the device and its size in kilowatts.
Utility approval and feesNo approval, fees or extra equipment beyond what the UL listing includes.
HOAs and property ownersFrom January 1, 2027: no one can unreasonably prohibit these devices; reasonable rules (notice, fire or overload, location) are allowed. In a common-interest community, an owner installing on their unit or its own patio, deck or balcony can be required to secure the device, cover liability and costs, and indemnify the association (§ 40-2-140(7)).
Codes and liabilityInstallation must follow fire code and local building codes (§ 40-2-140(9)). The utility isn’t liable for damage or injury from the device (§ 40-2-140(8)).
Meter collar adaptersThe Public Utilities Commission must adopt rules by December 31, 2026 for approving customer-owned adapters certified to UL 414.

In the law’s words

Short excerpts from HB 26-1007, Session Laws 2026, Chapter 127 (C.R.S. § 40-2-140); new text, printed in capitals in the session law, shown in normal case, quoted as written and checked word for word against the official text on October 13, 2026; each with what it means for a plug-in design.

11 excerpts with what each means

What it means for your design

Designs that fit, and one that doesn’t

391 W tierOne panel on a Hoymiles HiFlow Pro 391 LV, plugged into an existing outdoor GFCI outlet.
Above 391 WAn APsystems EZ1-LV (900 VA), installed by a licensed electrical contractor.
Full sizeUp to 1,920 W on a dedicated 20 A circuit, installed by a licensed electrician.

The engineering behind it

Why the circuit matters as much as the law, in four short points.

Circuit current, continuous output, outdoor outlets, AC vs panel watts

Why the circuit matters. A plug-in inverter pushes current into a branch circuit from the outlet end. The breaker in your panel only sees the current coming from the panel, not what the inverter adds. With other loads on the same circuit, part of the wire can carry the breaker’s full rating plus the inverter’s output without anything tripping. At 1,200 W the inverter adds 10 A at 120 V. That’s why we recommend a dedicated circuit for any plug-in system, even where the law doesn’t require one.

Continuous output. Code treats inverter output as continuous and sizes the circuit at 125% of it (NEC 705.28): 1,200 W is 10 A, times 1.25 is 12.5 A, which fits a 15 A circuit. Anything over 1,440 W needs a 20 A circuit.

Outdoors. Outdoor receptacles need GFCI protection (NEC 210.8) and an in-use weatherproof cover (NEC 406.9).

AC, not panel watts. These laws limit what the inverter puts out, not what the panels are rated for. You can put more panel on a small inverter; it trims the brightest hours and fills out the rest of the day. The Designer models that trimming hour by hour.

Design your systemSee Colorado on the map

Questions

Is plug-in solar legal in Colorado?

Yes. HB 26-1007 took effect August 12, 2026, allowing one system per address up to 1,920 W.

Do I need an electrician for plug-in solar in Colorado?

Not for devices of 391 W or less. Above 391 W, plan on it: the law exempts only devices of 391 W or less from Colorado’s solar installation law (C.R.S. 40-2-128), which requires AC-side work by a licensed electrical contractor and on-site supervision by a NABCEP-certified PV professional or a licensed electrician.

Can I plug 1,920 W into a regular outlet?

Not safely on a standard 15 A circuit. 1,920 W is 16 A at 120 V, and code sizes the circuit at 125% of continuous output, which is 20 A. Plan a dedicated 20 A circuit.

Sources

Bill text read September 29, 2026; law checked October 13, 2026 by Casey Schuyler, NABCEP PV Associate and O&M Associate Technician, Sun Safe LLC. Information for planning, not legal advice. Laws change; verify against the bill and your local authority having jurisdiction. Sun Safe’s position: installations should be code-compliant, and a practicing electrician is recommended.