Sun Safe LLC

Plug-In Solar in Maine

The law, and what it means for your design.

Plug-in solar by state › Maine

In effect

Law checked Oct 13, 2026 against P.L. 2025, c. 644 as enacted · Last change: three listing paths, net energy billing wording, liability and structure rules · Change log

Maine is the only state with a true two-tier law for plug-in solar. Up to 420 W is plug-and-play. Between 420 W and 1,200 W, a Maine-licensed electrician installs each system on its own circuit and you tell the utility. The 420 W line shapes almost every design decision.

What you can build today

No confirmed path. UL 3700: no complete system certified. Comparable standard: the component certificates need parts not on sale. NEC route: confirm the adopted code has a method with the Electricians’ Examining Board.

Always an option: a permitted, hardwired system under NEC 690 and 705 with your utility’s approval, or an off-grid power station that never connects to house wiring. UL Solutions notes the 2026 NEC “does not recognize the use of plug-in photovoltaic (PIPV) modules”; NFPA expects them in the 2029 edition (source). Where a law requires the NEC and gives no size waiver, the inspector decides. Sun Safe’s reading, not legal advice.

Limit
420 W, or up to 1,200 W with an electrician
Law
LD 1730
Signed
April 6, 2026
Effective
July 29, 2026

What the law says

Tier 1Up to 420 W AC combined inverter output per service address. No electrician required by the law.
Tier 2Above 420 W up to 1,200 W AC. Each system installed by a Maine-licensed electrician on a dedicated circuit with a single outlet.
How it’s measuredCombined inverter output, AC, per service address. Plug-in batteries count toward it.
ListingOne of three: listed to UL 3700; listed to a comparable standard by a national testing lab; or configured to the NEC adopted by the Electricians’ Examining Board (§ 3475(1)(A)).
Outage protectionInverter set to shut off after 0.2 seconds when power is disrupted.
Utility noticeTier 2 only: notify the utility within 30 days of installation on the Public Utilities Commission’s form (service address, inverter capacity, compliance statement).
Utility approval and feesThe utility can’t require approval, an interconnection application, agreement or study, fees, or extra equipment, and can’t deny a system that follows these rules.
Power sent to the gridNot eligible for net energy billing (§ 3475(4)).
Utility liabilityThe utility isn’t liable for damage or injury from a compliant system (§ 3475(7)).
Not your buildingKeep the structure sound, follow building, fire and zoning codes, and restore it when you remove the system (§ 3475(8)).

In the law’s words

Short excerpts from P.L. 2025, c. 644 (LD 1730), 35-A M.R.S. § 3475, quoted as written and checked word for word against the official text on October 13, 2026; each with what it means for a plug-in design.

11 excerpts with what each means

What it means for your design

Designs that fit, and one that doesn’t

Tier 1One or two panels on a Hoymiles HiFlow Pro 420 LV, plugged into an existing outdoor GFCI outlet.
Tier 1Two 450 W panels on an APsystems EZ1-LV with its output set to 420 W.
Tier 2An EZ1-LV at its full 900 VA, installed by a Maine-licensed electrician on a new dedicated single-outlet circuit, with the utility notified within 30 days.
Doesn’t fitAnything over 1,200 W AC combined at one service address.

The engineering behind it

Why the circuit matters as much as the law, in four short points.

Circuit current, continuous output, outdoor outlets, AC vs panel watts

Why the circuit matters. A plug-in inverter pushes current into a branch circuit from the outlet end. The breaker in your panel only sees the current coming from the panel, not what the inverter adds. With other loads on the same circuit, part of the wire can carry the breaker’s full rating plus the inverter’s output without anything tripping. At 1,200 W the inverter adds 10 A at 120 V. That’s why we recommend a dedicated circuit for any plug-in system, even where the law doesn’t require one.

Continuous output. Code treats inverter output as continuous and sizes the circuit at 125% of it (NEC 705.28): 1,200 W is 10 A, times 1.25 is 12.5 A, which fits a 15 A circuit. Anything over 1,440 W needs a 20 A circuit.

Outdoors. Outdoor receptacles need GFCI protection (NEC 210.8) and an in-use weatherproof cover (NEC 406.9).

AC, not panel watts. These laws limit what the inverter puts out, not what the panels are rated for. You can put more panel on a small inverter; it trims the brightest hours and fills out the rest of the day. The Designer models that trimming hour by hour.

Design your systemSee Maine on the map

Questions

Is plug-in solar legal in Maine?

Yes. LD 1730 (P.L. 2025, c. 644) took effect July 29, 2026.

Do I need an electrician for plug-in solar in Maine?

Not up to 420 W AC. Above 420 W and up to 1,200 W, each system has to be installed by a Maine-licensed electrician on a dedicated circuit with a single outlet.

Do I have to tell my utility in Maine?

Only above 420 W. Then you notify the utility within 30 days of installing, on the Public Utilities Commission’s form.

Can I use a 900 W inverter in Maine without an electrician?

Only if its output is limited to 420 W. The cap is on AC output, so an inverter set to 420 W in its app stays in tier 1.

Sources

Bill text read September 29, 2026; law checked October 13, 2026 by Casey Schuyler, NABCEP PV Associate and O&M Associate Technician, Sun Safe LLC. Information for planning, not legal advice. Laws change; verify against the bill and your local authority having jurisdiction. Sun Safe’s position: installations should be code-compliant, and a practicing electrician is recommended.