Phase 1 results: seven trials, seven passes.

Across seven field trials on a shorted 255 W module, three on Aug 29 and four on Oct 22, 2026 (witnessed on site by the fire service), the sheet cut the module’s short-circuit current from 7.6–9.5 A to a few milliamps, every time, in full sun of 816–1,041 W/m². Two independent light meters under the sheet and three clamp meters on the conductor agreed on the result.

Each trial, chart and statistic is below; how it was measured is on the Method page.

Tests included

All tests tap to choose

Summary

Trials

Every box [1]–[38] plus Side 2 results for the selected tests.

Ranges recorded on the sheet (e.g. BT270 “5–7”) are scored at the higher value. “≥” = the under-sheet meter read 0, so 1 W/m² is used and OD is a lower bound. Open any trial in the field log for the full Side 1 and Side 2.

Archive

Open the archive all trials, newest first

Back up / restore this device

Open shows the full Side 1, Side 2 and photos in the field log, read-only, with the PDF ready to download or share. Published trials are marked; trials saved only on this device can be deleted here.

Charts

Current with the sheet on, and the sun

Each brown bar is the current still flowing through the shorted module with the sheet on, read by the BT270. The gold line above it is the sun hitting the panel at that moment, so you can see the result was not just a cloudy day. The orange dashed line is the 125 mA pass gate; the navy dashed line is the 40 mA shock threshold in the NFPA 70E 2027 draft.

Example, Trial 005. Trial 005 had the highest current of all seven: 11 mA, with the sun at 847 W/m². That is about a quarter of the 40 mA line and under a tenth of the gate.

* Test log cells

BT270 [31] mA per trial (bars, left axis) · sun on the panel with the sheet on [26] (strip above, same trials) · 125 mA = Stage 1 (S1) gate · 40 mA = NFPA 70E 2027 draft dc shock threshold, recorded, not a Phase 1 gate

Optical density, both meter pairs

Optical density (OD) is how much sunlight the sheet stops, counted in powers of ten: OD 2 lets through 1 part in 100, OD 3 lets through 1 part in 1,000. Each trial has two bars because two different meter pairs measured it, one under the sheet against one in open sun. Higher is better; every bar needs to clear the orange 2.3 line.

Example, Trial 005. In Trial 005 the AH-Sol meter under the sheet read 2.1 W/m² while the one in the sun read 890 W/m². 890 ÷ 2.1 is about 424, so roughly 1 part in 424 got through: OD 2.63. The DayStar under the sheet read 0, so its bar (2.93) is a floor; the true value is at least that.

* Test log cells

DayStar pair −log10([29] ÷ [26]), a “≥” floor when [29] reads 0 (Side 2 row 3c) · AH-Sol pair −log10([30] ÷ [27]), calculated here for comparison · minimum 2.3, target 2.5

The sun, every meter

Three different sun meters were read three times in every trial: before the short, shorted with no sheet, and with the sheet on. Each dot is one reading; the color is the meter. The shaded box is the range from the lowest to the highest of all nine. A short box means the meters agreed and the sun held steady through the trial.

Example, Trial 005. In Trial 005 all nine readings fell between 847 and 902 W/m², a spread of 55 W/m², about 6%. The AH-Sol (orange) read highest at every stage, which it does in every trial: that is a steady difference between meters, not the sun changing.

* Test log cells

Ambient W/m² from DayStar #1, AH-Sol #1 and Seaward 200R at each stage: before the short [13] [14] [15], shorted with no sheet [18] [19] [20], sheet on [26] [27] [28]. Shaded band = spread between all of them.

Current, every clamp

Three different clamp meters measured the current twice in every trial: shorted with no sheet (open circle, top) and with the sheet on (filled dot, bottom). The scale jumps by ten at each gridline so amps and milliamps fit on one chart. The line between the two dots is the drop the sheet caused.

Example, Trial 005. In Trial 005 the three clamps read 7.9, 7.81 and 8.0 A with no sheet, within 0.2 A of each other. With the sheet on, the Fluke and Seaward read 0 (drawn on the 1 mA floor, below what they can resolve) and the BT270, which reads to 1 mA, read 11 mA.

* Test log cells and the Fluke readings

Fluke 393, Seaward clamp and BT270: shorted with no sheet [16] [17] [23] (open) and with the sheet on [24] [25] [31] (filled). Log scale; a 0 reading is drawn on the 1 mA floor. Sun for the same trials is in the chart beside it.

The Fluke’s 200 mA and 100 mA readings (Trials 1 and 3, Aug 29). These are meter offset, not current through the sheet. With the clamp off the conductor, its zero check [32] read 0.2 A in both trials, the same as or more than its sheet-on reading [24] (0.2 A in Trial 1, 0.1 A in Trial 3). Subtracting the zero gives 0 A both times. The Fluke 393 FC reads in 0.1 A steps and is rated ±(2% + 5 digits), about ±0.5 A at these levels, so 0.1–0.2 A is inside its own uncertainty. The Fluke and Seaward clamps were not re-zeroed on Aug 29; from Oct 22 the Fluke read 0.0 A, zero and sheet-on, in every trial. The BT270, which reads to 1 mA (±5 mA), read 2–8 mA in the same trials. Under the test plan, a Fluke reading at or below its own zero passes check 2a, and a zero of 200 mA or more means re-zero before the next trial (see Method).

Irradiance vs current collapse

Each trial is one vertical line: the open circle at the top is the current with the module shorted and no sheet, the filled dot at the bottom is the current with the sheet on. Left to right is how strong the sun was. The scale jumps by ten at each gridline, so the length of each line shows how many times smaller the current became.

Example, Trial 005. Trial 005 sits at 847 W/m² of sun: 8.0 A with no sheet, 11 mA with the sheet on. That is about 727 times less current, a 99.86% drop. Stronger sun (#1 and #2, right side) did not push the sheet-on current up.

* Test log cells

Each trial: shorted current before the sheet (open circle, highest of [16] [17] [23]) dropping to BT270 current with the sheet on (filled, [31]), placed by the sun with the sheet on [26]. Log scale: each gridline is 10×.

Statistics

N = . Trial 1 (Aug 29) has no Voc baseline, so Voc reduction covers the other trials. Its BT270 reading includes a 5 mA zero offset noted on the sheet (7 − 5 = 2 mA net); the table scores the raw 7 mA. Fluke readings at or below that meter’s own zero check pass 2a (Aug 29 trial 1: 200 mA vs a 200 mA zero).

Oct 22, 2026 testing

Mark Foote recording readings on siteTest stand and instrument board before the sheet, Trial 006

From the body camera: the witness entering readings during Trial 005, and the stand before the sheet in Trial 006.

Extrapolated: the largest module, full strings

What the sheet would do to the largest monofacial module in the calculations, on the brightest design day, alone and wired into strings for the three common system voltages. In series the voltage adds but the current stays the same, so the current collapses by the same factor in every string.

ModuleTrina Solar Vertex TSM-DE21, 670 W, monofacial (white backsheet) · datasheet
Isc (STC)18.62 A
Voc (STC)46.1 V
Max system voltage1,500 V DC
Design day1,400 W/m² (UL 2011): Isc = 18.62 × 1.4 = 26.07 A
Sheet on18.62 × 0.00149 × 1,400 = 38.8 mA · 46.1 × (8.3 ÷ 38.0) = 10.1 V per module
StringSystemNo sheet: voltageNo sheet: currentSheet on: voltageSheet on: current
Single module—46.1 V26.07 A10.1 V38.8 mA
13 modules600 V599.3 V26.07 A130.9 V38.8 mA
21 modules1,000 V968.1 V26.07 A211.5 V38.8 mA
32 modules1,500 V1,475.2 V26.07 A322.2 V38.8 mA

Example, 1,500 V string. With no sheet, a 32-module string on the design day sits at 1,475 V and can push 26.07 A through a short. With the sheet on, it would read about 322 V and 38.8 mA: the current about 670 times smaller, the voltage about 4.6 times smaller.

* Inputs and limits

No sheet: Isc scales with sunlight: 18.62 A × 1,400 ÷ 1,000 = 26.07 A. Voltage = modules × 46.1 V (nameplate Voc). Modules per string = system voltage ÷ 46.1 V, rounded down: 13, 21, 32 (no cold-weather correction, for comparison only).

Sheet on, current: I = Isc × T × G = 18.62 × 0.00149 × 1,400 = 38.8 mA, using the worst measured transmission (Trial 005, T = 0.00149), as on the Method page.

Sheet on, voltage: 10.1 V per module = 46.1 V × (8.3 ÷ 38.0), the highest sheet-on to nameplate ratio measured on the test module (Trial 007), carried over to this module.

Limits: Extrapolated from one test module; not measured on this module or on full strings. Transmission is assumed constant at any sun level; Phase 1 tested up to 1,055 W/m². Voltage under very low light depends on the cell type, so the sheet-on voltage is the least certain number here.